Flush 2 relays module responds to commands ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system. When Q1 relay is ON it goes automatically OFF after set time. The timer is reset to zero every time the module receives an ON command from any source. Value is in 1s or 10ms depending on parameter 15 When Q1 relay is OFF it goes automatically ON after set time. The timer is reset to zero every time the module receives an OFF command from any source. Value is in 1s or 10ms depending on parameter 15 When Q2 relay is ON it goes automatically OFF after set time. The timer is reset to zero every time the module receives an ON command from any source. Value is in 1s or 10ms depending on parameter 15 When Q2 relay is OFF it goes automatically ON after set time. The timer is reset to zero every time the module receives an OFF command from any source. Value is in 1s or 10ms depending on parameter 15 Select the time units for auto on/off configuration. Applies tot he whole device Set value from 0 - 100 (0%- 100%). 0 - Reporting Disabled. 1 - 100 = 1% - 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time change for more than set percentage comparing to previous actual power in Watts, step is 1%. Default value 1 Set value from 0 - 100 (0%- 100%). 0 - Reporting Disabled. 1 - 100 = 1% - 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time change for more than set percentage comparing to previous actual power in Watts, step is 1%. Default value 1 Set value means time interval (0 1 65535) in seconds, when power report is send. 0 - Reporting Disabled. 1 - 65535 = 1 second - 65535 seconds. Reporting enabled. Power report is send with time interval set by entered value. Default value 300 (power report in Watts is send each 300s) Set value means time interval (0 1 65535) in seconds, when power report is send. 0 - Reporting Disabled. 1 - 65535 = 1 second - 65535 seconds. Reporting enabled. Power report is send with time interval set by entered value. Default value 300 (power report in Watts is send each 300s) Type of device that is connected to the output (NC or NO) Type of device that is connected to the output (NC or NO)