Flush on off thermostat module responds to commands ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system.
When I2 is pressed set point will be set according to the value of this parameter.
Default value 65535 - Input I2 does not influence the setpoint.
0 - 990 - Setpoint from 0.0°C to 99.0°C.
1001 - 1150 - Setpoint from -0.1°C to -15.0°C.
When I3 is pressed set point will be set according to the value of this parameter.
Default value 65535 - Input I3 does not influence the setpoint.
0 - 990 - Setpoint from 0.0°C to 99.0°C.
1001 - 1150 - Setpoint from -0.1°C to -15.0°C.
Set value from 0 - 100 (0% - 100%). 0 - Reporting Disabled. 1 - 100 = 1% - 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time change for more than set percentage comparing to previous actual power in Watts, step is 1%. Default value 3
Set value means time interval (0 - 65535) in seconds, when power report is send. 0 - Reporting Disabled. 1 - 65535 = 1 second - 65535 seconds. Reporting enabled. Power report is send with time interval set by entered value. Default value 300 (power report in Watts is send each 300s)
This parameter defines temperature min difference between real measured temperature and set-point temperature to turn heating on. The parameter can be set from 0 to 255 where 0 to 127 means from 0.0 °C to 12.7 °C and from 128 to 255 means from - 0.1 °C to -12.7 °C.
This parameter defines temperature min difference between real measured temperature and set-point temperature to turn heating off. The parameter can be set from 0 to 255 where 0 to 127 means from 0.0 °C to 12.7 °C and from 128 to 255 means from - 0.0 °C to -12.7 °C.
Set value means at which temperature the heating will be turned on even if the thermostat was manually set to off. The parameter can be set from 0 to 255 where 0 to 128 means from 0.0 °C to 12.8 °C and from 129 to 255 means from - 0.0 °C to -12.8 °C.
Too low temperature limit is set by entering the value from 1 - 1000 (0,1°C to 100,0 °C). In case the value is set outside this range the module sets the value to default.
Too high temperature limit is set by entering the value from 1 - 1000 (0,1°C to 100,0 °C). In case the value is set outside this range the module sets the value to default.
Set value means the type of the heating device that is connected to the relay output. The heating device type can be normally open (NO) or normally close (NC).