Flush on off thermostat module responds to commands ALL ON / ALL OFF that may be sent by the main controller or by other controller belonging to the system. Default value 1 - Input I1 changes the mode of the thermostat between On and Off. In this case the function on window sensor is disabled. 32767 - Input I1 doesn't influence the heat/cool process. 2 - Input I1 influences on the cooling and heating valves according to status of window sensor. In this case function of Off and On selection by I1 is disabled. Default value 32767 - input I2 does not influence the heat/cool process. 0 - 990 Temperature setpoint from 0,0°C to 99,0°C. When I2 is pressed, it automatically sets the temperature setpoint to the value defined here. In this case the function of the condensation sensor is disabled. 1001 - 1150 Temperature setpoint from -0,1°C to -15,0°C. When I2 is pressed, it automatically sets the temperature setpoint to the value defined here. In this case the function of the condensation sensor is disabled. 2000 - Input I2 influences on the cooling valve according to status of condense sensor. In this case function of setpoint selection with I2 is disabled. Default value 32767 - input I3 does not influence the heat/cool process. 1 - input I3 changes the mode of the thermostat between Heat and Cool. In this case function on the flood sensor is disabled. 2 - input I3 influences cooling and heating valves according to the status of flood sensor. In this case function of Heat and Cool selection by I3 is disabled. Set value from 0 - 100 (0% - 100%). 0 - Reporting Disabled. 1 - 100 = 1% - 100% Reporting enabled. Power report is send (push) only when actual power in Watts in real time change for more than set percentage comparing to previous actual power in Watts, step is 1%. Default value 0 Set value means time interval (0 - 32767) in seconds, when power report is send. 0 - Reporting Disabled. 1 - 32767 = 1 second - 32767 seconds. Reporting enabled. Power report is send with time interval set by entered value. Default value 300 (power report in Watts is send each 300s) Set value means at which temperature the heating will be turned on even if the thermostat was manually set to off. The parameter can be set from 0 to 255 where 0 to 127 means from 0.0 °C to 12.7 °C and from 128 to 254 means from - 0.0 °C to -12.6 °C. The value 255 means that the Antifreeze functionality is disabled.Note; this functionality is activated only in heating mode. This parameter sets the minimum PWM percentage value that the PWM output stays on. Note, the minimum level may not exceed the maximum level. Default value 0. 2 - 100 = 2% to 100% seconds, step is 1%. This parameter sets the minimum PWM percentage value that the PWM output stays on. Note, the minimum level may not exceed the maximum level. Default value 0. 1 - 99 = 1% to 99% seconds, step is 1%. PWM cycle duration defines the sum of all ON and OFF time periods. Setting the parameter sets the PWM duty cycle to that value in seconds. Default value 10. 5 - 127 = 0 seconds to 127 seconds, step is 1 second This parameter defines the zone in which PID is not active. If the temperature difference between actual and setpoint is bigger than PID deadband, then the PID will start to regulate the system, otherwise PID is zero or fixed. Default value 5. 0 - 127 = 0,0 °C to 12,7 °C, step is 0,1°C This parameter defines the time between samples. On each sample time duration the controller will calculate the differrence between setpoint and actual temperature. Default value 5. 0 - 127 = 0 seconds to 127 seconds, step is 1 second Default value 100 0 - 1000 P value, step is 1 Default value 1 0 - 1000 I value, step is 1 Default value 1 0 - 1000 D value, step is 1 Too low temperature limit is set by entering the value from 1 - 1000 (0,1°C to 100,0 °C). In case the value is set outside this range the module sets the value to default. Too high temperature limit is set by entering the value from 1 - 1000 (0,1°C to 100,0 °C). In case the value is set outside this range the module sets the value to default. Set value means the type of the heating device that is connected to the PWM output. The heating device type can be normally open (NO) or normally close (NC). If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. If the value of parameter is different to 0 it means that the influence of this input to heating or cooling will react after inserted time. NOTE: Device status on the UI is changed immediately. Default value 0. 1 - 32000 seconds. Enabling I1 means that the Endpoint I1 will be present on the UI. Disabling it will result in hiding the endpoint according to the parameter set value. Additionally, a notification type and event can be selected for the endpoint. Enabling I2 means that the Endpoint I2 will be present on the UI. Disabling it will result in hiding the endpoint according to the parameter set value. Additionally, a notification type and event can be selected for the endpoint. Enabling I3 means that the Endpoint I3 will be present on the UI. Disabling it will result in hiding the endpoint according to the parameter set value. Additionally, a notification type and event can be selected for the endpoint. Set value is added or subtracted to actual measured value by the sensor. Default value 32536 1 - 100 = value from 0,1°C to 10,0°C is added to actual measured temperature 1001 - 1100 = value from -0,1°C to - 10,0°C is subtracted from actual measured temperature When temperature sensor is connected the module reports measured temperature on temperature change defined by this parameter. Default value 5 = 0,5°C. 0 - Reporting disabled 1 - 127 = 0,1°C - 12,7°C, step is 0,1°C