0 = Gas/Elec, 1 = HeatPump
0 = Gas, 1 = Elec
0 = w/Cool, 1 = w/Heat
0 = C, 1 = F
0 = Unlocked, 1 = Locked
Sets the minimum off time before another heating/cooling cycle can begin to provide compressor short cycle protection. The thermostat screen will display WAIT when minimum off time is being enforced.
Sets the minimum run time before a heating/cooling cycle can turn off to prevent rapid cycling. Thermostat screen will display "Cool ON" or "Heat ON" while the minimum run time is being enforced.
Sets the delta from setpoint that stage 1 heating starts.
Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at setpoint minus (-) Delta Stage 1.
Sets the delta from setpoint that stage 2 heating starts.
Sets the delta from setpoint that stage 2 heating stops. Stage 1 turns off at setpoint minus (-) Delta Stage 2.
Sets the delta from setpoint that stage 3 heating starts.
Sets the delta from setpoint that stage 3 heating stops. Stage 1 turns off at setpoint minus (-) Delta Stage 3.
Sets the delta from setpoint that stage 1 cooling starts.
Sets the delta from setpoint that stage 1 cooling stops. Stage 1 turns off at setpoint minus (-) Delta Stage 1.
Sets the delta from setpoint that stage 2 cooling starts.
Sets the delta from setpoint that stage 2 cooling stops. Stage 1 turns off at setpoint minus (-) Delta Stage 2.
Sets the minimum separation between the heating and cooling setpoints. Attempts to lower the cooling below the heating setpoint by this amount will PUSH the heating setpoint down to maintain this separation. Same for setting the heating setpoint above the cooling setpoint, it will PUSH the cooling setpoint up to maintain this separation. Settings in F.
0 = No Setback, 1 = Setback, 2 if ESM
Energy Saving Mode (ESM) Setpoints are the setpoints used when the Energy Saving Mode schedule is selected in the Schedule Mode screen (or via Z-Wave control). Setting in F.
Energy Saving Mode (ESM) Setpoints are the setpoints used when the Energy Saving Mode schedule is selected in the Schedule Mode screen (or via Z-Wave control).
The fan cycler function cycles the HVAC system fan for an ON period followed by an OFF period continuously. Used to provide minimum air ventilation requirements. When the Fan ON time is set to a value greater than 0, an additional Cycler Fan mode is present when pressing the FAN button on the thermostat.
The fan cycler function cycles the HVAC system fan for an ON period followed by an OFF period continuously. Used to provide minimum air ventilation requirements. When the Fan ON time is set to a value greater than 0, an additional Cycler Fan mode is present when pressing the FAN button on the thermostat.
0 = no 2nd stage heat, 1 = 2nd stage heat.
0 = no aux heat, 1 = aux heat enabled.
0 = no 2nd stage cool, 1 = 2nd stage cool
Set to 1 if running schedule (RUN is displayed on the thermostat screen).
Default:
HOLD 80F / 26C
RUN 84F / xxC
ESM
Heating 1 Setpoint (does this vary with ESM, etc. or is this for the "Hold" setting?
Default:
HOLD 55F / 13C
RUN 60F / xxC
ESM 64F / xxC (unless parameter xx has been changed)
Backlight Timeout is the time (in seconds) from the last
button press to the backlight going out. The time-out
can be set between 0 and 120
seconds. When set to 0, the backlight will remain
always on.
Default: 30
Sets the maximum heating setpoint value. Will not ramp
or accept setpoints higher than this maximum.
Minimum: 55F / xxC
Maximum: 90F / xxC
Default: 90F / 32C
Sets the minimum cooling setpoint value. Will not ramp
or accept setpoints lower than this minimum.
Minimum: 60F / xxC
Maximum: 99F / xxC
Default: 60F / 15C
This is the time before any screen reverts to the Minimized
Screen (temperature display only), after you stop pushing
buttons. Minimized Screen feature is disabled by setting this
time to 0.
Default: 0
The internal temperature sensor can be calibrated to report
values different from its actual reading. The offset can
range from -7 degrees to +7 degrees.
Default: 0
The Screen Contrast sets the contrast level of the LCD display.
The contrast can be set between 0 and 20. If the display
is too light, use a higher number. If dark lines appear on
the screen, use a lower number.
Default: 10
0x2c after reset
0xf4 after reset
0x2c after reset
0xf4 after reset
0xb8 after reset
0xe4 after reset
0xb8 after reset
0xe4 after reset
When enabled (set to 1), the local thermostat's scheduler
function is enabled.
Default: 0
0xff after reset
0xff after reset
0xff after reset
0xff after reset
0xff after reset
0xff after reset
0xff after reset
Recovery enable?
Default: 1
0x00
This value holds information about the first schedule
setpoints for Sundays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule
setpoints for Sundays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule
setpoints for Sundays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule
setpoints for Sundays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule
setpoints for Mondays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule
setpoints for Mondays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule
setpoints for Mondays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule
setpoints for Mondays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule
setpoints for Tuesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule
setpoints for Tuesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule
setpoints for Tuesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule
setpoints for Tuesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule
setpoints for Wednesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule setpoints for Wednesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule setpoints for Wednesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule setpoints for Wednesdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule setpoints for Thursdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule setpoints for Thursdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule setpoints for Thursdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule setpoints for Thursdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule setpoints for Fridays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule setpoints for Fridays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule setpoints for Fridays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule setpoints for Fridays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C
This value holds information about the first schedule setpoints for Saturdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x06004643 06:00AM 70F / 67F
0x06001519 06:00AM 21C / 25C
This value holds information about the second schedule setpoints for Saturdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x08003e55 08:00AM 62F / 85F
0x0800101d 08:00AM 16C / 29C
This value holds information about the third schedule setpoints for Saturdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x1200464e 06:00PM 70F / 78F
0x12001519 06:00PM 21C / 25C
This value holds information about the fourth schedule setpoints for Saturdays.
Byte 1: Hour (0-23)
Byte 2: Minute (0-59)
Byte 3: Heat Setpoint (degrees)
Byte 4: Cool Setpoint (degrees)
Default: 0x16003e52 10:00PM 62F / 82F
0x1600101b 10:00PM 16C / 27C