**Parameter**;**Datatype**;**Value Range**;**Explanation** name;string;;name of the transformer std_type;string;;transformer standard type name hv_bus*;integer;;high voltage bus index of the transformer lv_bus*;integer;;low voltage bus index of the transformer sn_mva*;float;:math:`>` 0;rated apparent power of the transformer [MVA] vn_hv_kv*;float;:math:`>` 0;rated voltage at high voltage bus [kV] vn_lv_kv*;float;:math:`>` 0;rated voltage at low voltage bus [kV] vk_percent*;float;:math:`>` 0;short circuit voltage [%] vkr_percent*;float;:math:`\geq` 0;"real component of short circuit voltage [%]" pfe_kw*;float;:math:`\geq` 0;iron losses [kW] i0_percent*;float;:math:`\geq` 0;open loop losses in [%] vk0_percent***;float;:math:`\geq` 0;zero sequence relative short-circuit voltage vkr0_percent***;float;:math:`\geq` 0;real part of zero sequence relative short-circuit voltage mag0_percent***;float;:math:`\geq` 0;ratio between magnetizing and short circuit impedance (zero sequence) mag0_rx***;float;;zero sequence magnetizing r/x ratio si0_hv_partial***;float;:math:`\geq` 0;zero sequence short circuit impedance distribution in hv side vector_group***;String;'Dyn','Yyn','Yzn','YNyn'; Vector Groups ( required for zero sequence model of transformer ) shift_degree*;float;;transformer phase shift angle tap_side;string;"""hv"", ""lv""";defines if tap changer is at the high- or low voltage side tap_neutral;integer;;rated tap position tap_min;integer;;minimum tap position tap_max;integer;;maximum tap position tap_step_percent;float;:math:`>` 0;tap step size for voltage magnitude [%] tap_step_degree;float;:math:`\geq` 0;tap step size for voltage angle tap_pos;integer;;current position of tap changer tap_phase_shifter;bool;;defines whether the transformer is an ideal phase shifter parallel;int;:math:`>` 0;number of parallel transformers max_loading_percent**;float;:math:`>` 0;Maximum loading of the transformer with respect to sn_mva and its corresponding current at 1.0 p.u. df;float;1 :math:`\geq` df :math:`>` 0;derating factor: maximal current of transformer in relation to nominal current of transformer (from 0 to 1) in_service*;boolean;True / False;specifies if the transformer is in service oltc*;boolean;True / False; specifies if the transformer has an OLTC (short-circuit relevant) power_station_unit*;boolean;True / False; specifies if the transformer is part of a power_station_unit (short-circuit relevant).