{ "group": { "desc": "Immediate Inverter Controls ", "label": "Immediate Controls", "name": "controls", "points": [ { "desc": "Model identifier", "label": "Model ID", "mandatory": "M", "name": "ID", "size": 1, "static": "S", "type": "uint16", "value": 123 }, { "desc": "Model length", "label": "Model Length", "mandatory": "M", "name": "L", "size": 1, "static": "S", "type": "uint16" }, { "access": "RW", "desc": "Time window for connect/disconnect.", "label": "Conn_WinTms", "name": "Conn_WinTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Timeout period for connect/disconnect.", "label": "Conn_RvrtTms", "name": "Conn_RvrtTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Enumerated valued. Connection control.", "label": "Conn", "mandatory": "M", "name": "Conn", "size": 1, "symbols": [ { "name": "DISCONNECT", "value": 0 }, { "name": "CONNECT", "value": 1 } ], "type": "enum16" }, { "access": "RW", "desc": "Set power output to specified level.", "label": "WMaxLimPct", "mandatory": "M", "name": "WMaxLimPct", "sf": "WMaxLimPct_SF", "size": 1, "type": "uint16", "units": "% WMax" }, { "access": "RW", "desc": "Time window for power limit change.", "label": "WMaxLimPct_WinTms", "name": "WMaxLimPct_WinTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Timeout period for power limit.", "label": "WMaxLimPct_RvrtTms", "name": "WMaxLimPct_RvrtTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Ramp time for moving from current setpoint to new setpoint.", "label": "WMaxLimPct_RmpTms", "name": "WMaxLimPct_RmpTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Enumerated valued. Throttle enable/disable control.", "label": "WMaxLim_Ena", "mandatory": "M", "name": "WMaxLim_Ena", "size": 1, "symbols": [ { "name": "DISABLED", "value": 0 }, { "name": "ENABLED", "value": 1 } ], "type": "enum16" }, { "access": "RW", "desc": "Set power factor to specific value - cosine of angle.", "label": "OutPFSet", "mandatory": "M", "name": "OutPFSet", "sf": "OutPFSet_SF", "size": 1, "type": "int16", "units": "cos()" }, { "access": "RW", "desc": "Time window for power factor change.", "label": "OutPFSet_WinTms", "name": "OutPFSet_WinTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Timeout period for power factor.", "label": "OutPFSet_RvrtTms", "name": "OutPFSet_RvrtTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Ramp time for moving from current setpoint to new setpoint.", "label": "OutPFSet_RmpTms", "name": "OutPFSet_RmpTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Enumerated valued. Fixed power factor enable/disable control.", "label": "OutPFSet_Ena", "mandatory": "M", "name": "OutPFSet_Ena", "size": 1, "symbols": [ { "name": "DISABLED", "value": 0 }, { "name": "ENABLED", "value": 1 } ], "type": "enum16" }, { "access": "RW", "desc": "Reactive power in percent of WMax.", "label": "VArWMaxPct", "name": "VArWMaxPct", "sf": "VArPct_SF", "size": 1, "type": "int16", "units": "% WMax" }, { "access": "RW", "desc": "Reactive power in percent of VArMax.", "label": "VArMaxPct", "name": "VArMaxPct", "sf": "VArPct_SF", "size": 1, "type": "int16", "units": "% VArMax" }, { "access": "RW", "desc": "Reactive power in percent of VArAval.", "label": "VArAvalPct", "name": "VArAvalPct", "sf": "VArPct_SF", "size": 1, "type": "int16", "units": "% VArAval" }, { "access": "RW", "desc": "Time window for VAR limit change.", "label": "VArPct_WinTms", "name": "VArPct_WinTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Timeout period for VAR limit.", "label": "VArPct_RvrtTms", "name": "VArPct_RvrtTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Ramp time for moving from current setpoint to new setpoint.", "label": "VArPct_RmpTms", "name": "VArPct_RmpTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "Enumerated value. VAR percent limit mode.", "label": "VArPct_Mod", "name": "VArPct_Mod", "size": 1, "symbols": [ { "name": "NONE", "value": 0 }, { "name": "WMax", "value": 1 }, { "name": "VArMax", "value": 2 }, { "name": "VArAval", "value": 3 } ], "type": "enum16" }, { "access": "RW", "desc": "Enumerated valued. Percent limit VAr enable/disable control.", "label": "VArPct_Ena", "mandatory": "M", "name": "VArPct_Ena", "size": 1, "symbols": [ { "name": "DISABLED", "value": 0 }, { "name": "ENABLED", "value": 1 } ], "type": "enum16" }, { "desc": "Scale factor for power output percent.", "label": "WMaxLimPct_SF", "mandatory": "M", "name": "WMaxLimPct_SF", "size": 1, "type": "sunssf" }, { "desc": "Scale factor for power factor.", "label": "OutPFSet_SF", "mandatory": "M", "name": "OutPFSet_SF", "size": 1, "type": "sunssf" }, { "desc": "Scale factor for reactive power percent.", "label": "VArPct_SF", "name": "VArPct_SF", "size": 1, "type": "sunssf" } ], "type": "group" }, "id": 123 }