{ "group": { "desc": "Dynamic Reactive Current ", "label": "Dynamic Reactive Current", "name": "reactive_current", "points": [ { "desc": "Model identifier", "label": "Model ID", "mandatory": "M", "name": "ID", "size": 1, "static": "S", "type": "uint16", "value": 128 }, { "desc": "Model length", "label": "Model Length", "mandatory": "M", "name": "L", "size": 1, "static": "S", "type": "uint16" }, { "access": "RW", "desc": "Indicates if gradients trend toward zero at the edges of the deadband or trend toward zero at the center of the deadband.", "label": "ArGraMod", "mandatory": "M", "name": "ArGraMod", "size": 1, "symbols": [ { "name": "EDGE", "value": 0 }, { "name": "CENTER", "value": 1 } ], "type": "enum16" }, { "access": "RW", "desc": "The gradient used to increase capacitive dynamic current. A value of 0 indicates no additional reactive current support.", "label": "ArGraSag", "mandatory": "M", "name": "ArGraSag", "sf": "ArGra_SF", "size": 1, "type": "uint16", "units": "%ARtg/%dV" }, { "access": "RW", "desc": "The gradient used to increase inductive dynamic current. A value of 0 indicates no additional reactive current support.", "label": "ArGraSwell", "mandatory": "M", "name": "ArGraSwell", "sf": "ArGra_SF", "size": 1, "type": "uint16", "units": "%ARtg/%dV" }, { "access": "RW", "desc": "Activate dynamic reactive current model", "label": "ModEna", "mandatory": "M", "name": "ModEna", "size": 1, "symbols": [ { "name": "ENABLED", "value": 0 } ], "type": "bitfield16" }, { "access": "RW", "desc": "The time window used to calculate the moving average voltage.", "label": "FilTms", "name": "FilTms", "size": 1, "type": "uint16", "units": "Secs" }, { "access": "RW", "desc": "The lower delta voltage limit for which negative voltage deviations less than this value no dynamic vars are produced.", "label": "DbVMin", "name": "DbVMin", "sf": "VRefPct_SF", "size": 1, "type": "uint16", "units": "% VRef" }, { "access": "RW", "desc": "The upper delta voltage limit for which positive voltage deviations less than this value no dynamic current produced.", "label": "DbVMax", "name": "DbVMax", "sf": "VRefPct_SF", "size": 1, "type": "uint16", "units": "% VRef" }, { "access": "RW", "desc": "Block zone voltage which defines a lower voltage boundary below which no dynamic current is produced.", "label": "BlkZnV", "name": "BlkZnV", "sf": "VRefPct_SF", "size": 1, "type": "uint16", "units": "% VRef" }, { "access": "RW", "desc": "Hysteresis voltage used with BlkZnV.", "label": "HysBlkZnV", "name": "HysBlkZnV", "sf": "VRefPct_SF", "size": 1, "type": "uint16", "units": "% VRef" }, { "access": "RW", "desc": "Block zone time the time before which reactive current support remains active regardless of how low the voltage drops.", "label": "BlkZnTmms", "name": "BlkZnTmms", "size": 1, "type": "uint16", "units": "mSecs" }, { "access": "RW", "desc": "Hold time during which reactive current support continues after the average voltage has entered the dead zone.", "label": "HoldTmms", "name": "HoldTmms", "size": 1, "type": "uint16", "units": "mSecs" }, { "desc": "Scale factor for the gradients.", "label": "ArGra_SF", "mandatory": "M", "name": "ArGra_SF", "size": 1, "type": "sunssf" }, { "desc": "Scale factor for the voltage zone and limit settings.", "label": "VRefPct_SF", "name": "VRefPct_SF", "size": 1, "type": "sunssf" }, { "name": "Pad", "size": 1, "type": "pad" } ], "type": "group" }, "id": 128 }