{ "group": { "desc": "DER Frequency Droop model.", "groups": [ { "comments": [ "Stored control sets - Number of control sets contained in NCtl - The first set is read-only and indicates the current settings." ], "count": "NCtl", "desc": "Stored control sets.", "label": "Stored Controls", "name": "Ctl", "points": [ { "access": "RW", "desc": "The deadband value for over-frequency conditions in Hz.", "label": "Over-Frequency Deadband", "mandatory": "M", "name": "DbOf", "sf": "Db_SF", "size": 2, "type": "uint32", "units": "Hz", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "The deadband value for under-frequency conditions in Hz.", "label": "Under-Frequency Deadband", "mandatory": "M", "name": "DbUf", "sf": "Db_SF", "size": 2, "type": "uint32", "units": "Hz", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "Frequency droop per-unit frequency change for over-frequency conditions corresponding to 1 per-unit power output change.", "label": "Over-Frequency Change Ratio", "mandatory": "M", "name": "KOf", "sf": "K_SF", "size": 1, "type": "uint16", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "Frequency droop per-unit frequency change for under-frequency conditions corresponding to 1 per-unit power output change.", "label": "Under-Frequency Change Ratio", "mandatory": "M", "name": "KUf", "sf": "K_SF", "size": 1, "type": "uint16", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "The open-loop response time in seconds.", "label": "Open-Loop Response Time", "mandatory": "M", "name": "RspTms", "sf": "RspTms_SF", "size": 2, "type": "uint32", "units": "Secs", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "The minimum active power output due to DER prime mover constraints, in percent of the DER active power rating. The valid range is -100 to 100. This setting applies only to the frequency droop control.", "label": "Minimum Active Power", "name": "PMin", "size": 1, "type": "int16", "units": "Pct", "standards": [] }, { "desc": "Control read-write access.", "label": "Control Access", "mandatory": "M", "name": "ReadOnly", "size": 1, "static": "S", "symbols": [ { "desc": "Control has read-write access.", "label": "Read-Write Access", "name": "RW", "value": 0 }, { "desc": "Control has read-only access.", "label": "Read-Only Access", "name": "R", "value": 1 } ], "type": "enum16", "standards": [ "IEEE 1547-2018" ] } ], "type": "group" } ], "label": "DER Frequency Droop", "name": "DERFreqDroop", "points": [ { "desc": "DER Frequency Droop model ID.", "label": "Model ID", "mandatory": "M", "name": "ID", "size": 1, "static": "S", "type": "uint16", "value": 711, "standards": [ "IEEE 1547-2018" ] }, { "desc": "DER Frequency Droop model length.", "label": "Model Length", "mandatory": "M", "name": "L", "size": 1, "static": "S", "type": "uint16", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "DER Frequency-Watt (Frequency-Droop) control enable.", "label": "DER Frequency Droop Module Enable", "mandatory": "M", "name": "Ena", "size": 1, "symbols": [ { "desc": "Function is disabled.", "label": "Disabled", "name": "DISABLED", "value": 0 }, { "desc": "Function is enabled.", "label": "Enabled", "name": "ENABLED", "value": 1 } ], "type": "enum16", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "Set active control. 0 = No active control.", "label": "Set Active Control Request", "mandatory": "M", "name": "AdptCtlReq", "size": 1, "type": "uint16", "standards": [ "IEEE 1547-2018" ] }, { "desc": "Result of last set active control operation.", "label": "Set Active Control Result", "mandatory": "M", "name": "AdptCtlRslt", "size": 1, "symbols": [ { "desc": "Control update in progress.", "label": "Update In Progress", "name": "IN_PROGRESS", "value": 0 }, { "desc": "Control update completed successfully.", "label": "Update Complete", "name": "COMPLETED", "value": 1 }, { "desc": "Control update failed.", "label": "Update Failed", "name": "FAILED", "value": 2 } ], "type": "enum16", "standards": [ "IEEE 1547-2018" ] }, { "desc": "Number of stored controls supported.", "label": "Stored Control Count", "mandatory": "M", "name": "NCtl", "size": 1, "static": "S", "type": "uint16", "standards": [ "IEEE 1547-2018" ] }, { "access": "RW", "desc": "Reversion time in seconds. 0 = No reversion time.", "label": "Reversion Timeout", "name": "RvrtTms", "size": 2, "type": "uint32", "units": "Secs", "standards": [] }, { "desc": "Reversion time remaining in seconds.", "label": "Reversion Time Left", "name": "RvrtRem", "size": 2, "type": "uint32", "units": "Secs", "standards": [] }, { "access": "RW", "desc": "Default control after reversion timeout.", "label": "Reversion Control", "name": "RvrtCtl", "size": 1, "type": "uint16", "standards": [] }, { "desc": "Deadband scale factor.", "label": "Deadband Scale Factor", "mandatory": "M", "name": "Db_SF", "size": 1, "static": "S", "type": "sunssf", "standards": [ "IEEE 1547-2018" ] }, { "desc": "Frequency change scale factor.", "label": "Frequency Change Scale Factor", "mandatory": "M", "name": "K_SF", "size": 1, "static": "S", "type": "sunssf", "standards": [ "IEEE 1547-2018" ] }, { "desc": "Open loop response time scale factor.", "label": "Open-Loop Scale Factor", "mandatory": "M", "name": "RspTms_SF", "size": 1, "static": "S", "type": "sunssf", "standards": [ "IEEE 1547-2018" ] } ], "type": "group" }, "id": 711 }