{ "group": { "desc": "DER Control", "label": "DERCtl", "name": "DERCtl", "points": [ { "desc": "DER control model ID.", "label": "Model ID", "mandatory": "M", "name": "ID", "size": 1, "static": "S", "type": "uint16", "value": 715 }, { "desc": "DER control model length.", "label": "Model Length", "mandatory": "M", "name": "L", "size": 1, "static": "S", "type": "uint16", "value": 7 }, { "comments": [ "DER Controls" ], "desc": "DER control mode. Enumeration.", "label": "Control Mode", "name": "LocRemCtl", "size": 1, "symbols": [ { "label": "Remote Control", "name": "REMOTE", "value": 0 }, { "desc": "Local mode is required for manual/maintenance operations. Once invoked, it must be explicitly exited for the inverter to be controlled remotely.", "label": "Local Control", "name": "LOCAL", "value": 1 } ], "type": "enum16" }, { "desc": "Value is incremented every second by the DER with periodic resets to zero.", "label": "DER Heartbeat", "name": "DERHb", "size": 2, "type": "uint32" }, { "access": "RW", "desc": "Value is incremented every second by the controller with periodic resets to zero.", "label": "Controller Heartbeat", "name": "ControllerHb", "size": 2, "type": "uint32" }, { "access": "RW", "desc": "Used to reset any latched alarms. 1 = Reset.", "label": "Alarm Reset", "name": "AlarmReset", "size": 1, "type": "uint16" }, { "access": "RW", "desc": "Commands to PCS. Enumerated value.", "label": "Set Operation", "name": "OpCtl", "size": 1, "symbols": [ { "label": "Stop the DER", "name": "STOP", "value": 0 }, { "label": "Start the DER", "name": "START", "value": 1 }, { "label": "Enter Standby Mode", "name": "ENTER_STANDBY", "value": 2 }, { "label": "Exit Standby Mode", "name": "EXIT_STANDBY", "value": 3 } ], "type": "enum16" } ], "type": "group" }, "id": 715 }