012301Static Volt-VAR Arrays Ref 3: 8.8.1.2Number of curves supported (recommend 4)Number of curve points supported (maximum of 20)Is Volt-VAR control activeIndex of active curve. 0 = no active curveTime window for volt-VAR changeTimeout period for volt-VAR curve selectionRamp time for moving from current mode to new modeScale factor for percent VRefOptional description for curve. (Max 16 chars)Number of active points in arrayMeaning of dependent variable: 1=%WMax 2=%VArMax 3=%VArAvalScale factor for dependent variableThe time of the PT1 in seconds (time to accomplish a change of 95%)The maximum rate at which the VAR value may be reduced in response to changes in the voltage value. %ref_value is %WMax %VArMax or %VArAval depending on value of DeptRefThe maximum rate at which the VAR value may be increased in response to changes in the voltage value. %ref_value is %WMax %VArMax or %VArAval depending on value of DeptRefPoint 1 VoltsPoint 1 VARsPoint 2 VoltsPoint 2 VARsPoint 2 VoltsPoint 3 VARsPoint 4 VoltsPoint 4 VARsPoint 5 VoltsPoint 5 VARsPoint 6 VoltsPoint 6 VARsPoint 7 VoltsPoint 7 VARsPoint 8 VoltsPoint 8 VARsPoint 9 VoltsPoint 9 VARsPoint 10 VoltsPoint 10 VARsPoint 11 VoltsPoint 11 VARsPoint 12 VoltsPoint 12 VARsPoint 13 VoltsPoint 13 VARsPoint 14 VoltsPoint 14 VARsPoint 15 VoltsPoint 15 VARsPoint 16 VoltsPoint 16 VARsPoint 17 VoltsPoint 17 VARsPoint 18 VoltsPoint 18 VARsPoint 19 VoltsPoint 19 VARsPoint 20 VoltsPoint 20 VARsBoolean flag indicates if curve is read-only or can be modified