0 1 2 3 0 1 Static Volt-VAR Arrays Ref 3: 8.8.1.2 Number of curves supported (recommend 4) Number of curve points supported (maximum of 20) Is Volt-VAR control active Index of active curve. 0 = no active curve Time window for volt-VAR change Timeout period for volt-VAR curve selection Ramp time for moving from current mode to new mode Scale factor for percent VRef Optional description for curve. (Max 16 chars) Number of active points in array Meaning of dependent variable: 1=%WMax 2=%VArMax 3=%VArAval Scale factor for dependent variable The time of the PT1 in seconds (time to accomplish a change of 95%) The maximum rate at which the VAR value may be reduced in response to changes in the voltage value. %ref_value is %WMax %VArMax or %VArAval depending on value of DeptRef The maximum rate at which the VAR value may be increased in response to changes in the voltage value. %ref_value is %WMax %VArMax or %VArAval depending on value of DeptRef Point 1 Volts Point 1 VARs Point 2 Volts Point 2 VARs Point 2 Volts Point 3 VARs Point 4 Volts Point 4 VARs Point 5 Volts Point 5 VARs Point 6 Volts Point 6 VARs Point 7 Volts Point 7 VARs Point 8 Volts Point 8 VARs Point 9 Volts Point 9 VARs Point 10 Volts Point 10 VARs Point 11 Volts Point 11 VARs Point 12 Volts Point 12 VARs Point 13 Volts Point 13 VARs Point 14 Volts Point 14 VARs Point 15 Volts Point 15 VARs Point 16 Volts Point 16 VARs Point 17 Volts Point 17 VARs Point 18 Volts Point 18 VARs Point 19 Volts Point 19 VARs Point 20 Volts Point 20 VARs Boolean flag indicates if curve is read-only or can be modified