0 0 1 Curve-Based Frequency-Watt Ref 3: 8.9.1.2, 8.9.4.2 Number of curves supported (recommend min. 4) Number of curve points supported (maximum of 10) Is curve-based Frequency-Watt control active Index of active curve. 0 = no active curve 1=enable snapshot/capture mode Reference active power (default = WMax) Frequency deviation from nominal frequency at the time of the snapshot to start constraining power output Frequency deviation from nominal frequency at which to release the power output Time window for freq-watt change Timeout period for freq-watt curve selection Ramp time for moving from current mode to new mode Scale factor for frequency Scale factor for percent WRef Scale factor for increment and decrement ramps Optional description for curve. (Max 16 chars) Number of active points in array The time of the PT1 in seconds (time to accomplish a change of 95%) The maximum rate at which the power value may be reduced in response to changes in the frequency value The maximum rate at which the power value may be increased in response to changes in the frequency value The maximum rate at which the power may be increased after releasing the frozen value of snap shot function. Point 1 Hertz Point 1 Watts Point 2 Hertz Point 2 Watts Point 3 Hertz Point 3 Watts Point 4 Hertz Point 4 Watts Point 5 Hertz Point 5 Watts Point 6 Hertz Point 6 Watts Point 7 Hertz Point 7 Watts Point 8 Hertz Point 8 Watts Point 9 Hertz Point 9 Watts Point 10 Hertz Point 10 Watts Point 11 Hertz Point 11 Watts Point 12 Hertz Point 12 Watts Point 13 Hertz Point 13 Watts Point 14 Hertz Point 14 Watts Point 15 Hertz Point 15 Watts Point 16 Hertz Point 16 Watts Point 17 Hertz Point 17 Watts Point 18 Hertz Point 18 Watts Point 19 Hertz Point 19 Watts Point 20 Hertz Point 20 Watts Enumerated value indicates if curve is read-only or can be modified