001Curve-Based Frequency-Watt Ref 3: 8.9.1.2, 8.9.4.2Number of curves supported (recommend min. 4)Number of curve points supported (maximum of 10)Is curve-based Frequency-Watt control activeIndex of active curve. 0 = no active curve1=enable snapshot/capture modeReference active power (default = WMax)Frequency deviation from nominal frequency at the time of the snapshot to start constraining power outputFrequency deviation from nominal frequency at which to release the power outputTime window for freq-watt changeTimeout period for freq-watt curve selectionRamp time for moving from current mode to new modeScale factor for frequencyScale factor for percent WRefScale factor for increment and decrement rampsOptional description for curve. (Max 16 chars)Number of active points in arrayThe time of the PT1 in seconds (time to accomplish a change of 95%)The maximum rate at which the power value may be reduced in response to changes in the frequency valueThe maximum rate at which the power value may be increased in response to changes in the frequency valueThe maximum rate at which the power may be increased after releasing the frozen value of snap shot function. Point 1 HertzPoint 1 WattsPoint 2 HertzPoint 2 WattsPoint 3 HertzPoint 3 WattsPoint 4 HertzPoint 4 WattsPoint 5 HertzPoint 5 WattsPoint 6 HertzPoint 6 WattsPoint 7 HertzPoint 7 WattsPoint 8 HertzPoint 8 WattsPoint 9 HertzPoint 9 WattsPoint 10 HertzPoint 10 WattsPoint 11 HertzPoint 11 WattsPoint 12 HertzPoint 12 WattsPoint 13 HertzPoint 13 WattsPoint 14 HertzPoint 14 WattsPoint 15 HertzPoint 15 WattsPoint 16 HertzPoint 16 WattsPoint 17 HertzPoint 17 WattsPoint 18 HertzPoint 18 WattsPoint 19 HertzPoint 19 WattsPoint 20 HertzPoint 20 WattsEnumerated value indicates if curve is read-only or can be modified