Many modbus devices support only one or very few clients. This proxy acts as a bridge between the client and the modbus device. It can be seen as a layer 7 reverse proxy. This allows multiple clients to communicate with the same modbus device.
When multiple clients are connected, cross messages are avoided by serializing communication on a first come first served REQ/REP basis.
This project is the Rust version of the Python based modbus-proxy project.
I did it because it fitted my personal goal of exercising with the Rust programming language and it's async based tokio library.
The goal was to produce a robust, highly concurrent server with a low memory footprint.
$ cargo install modbus-proxy-rs
First, you will need write a configuration file where you specify for each modbus device you which to control:
Configuration files can be written in YAML (.yml or .yaml) or TOML (.toml).
Suppose you have a PLC modbus device listening on plc1.acme.org:502 and you want your clients to connect to your machine on port 9000. A YAML configuration would look like this:
devices:
- modbus:
url: plc1.acme.org:502 # device url (mandatory)
listen:
bind: 0:9000 # listening address (mandatory)
Assuming you saved this file as modbus-config.yml
, start the server with:
$ modbus-proxy-rs -c ./modbus-config.yml
Now, instead of connecting your client(s) to plc1.acme.org:502
you just need to
tell them to connect to *machine*:9000
(where machine is the host where
modbus-proxy is running).
Note that the server is capable of handling multiple modbus devices. Here is a configuration example for 2 devices:
devices:
- modbus:
url: plc1.acme.org:502
listen:
bind: 0:9000
- modbus:
url: plc2.acme.org:502
listen:
bind: 0:9001
Log levels can be adjusted by setting the RUST_LOG
environment variable (default is warn
):
$ RUST_LOG=debug modbus-proxy-rs -c ./modbus-config.yml
This project ships with a Dockerfile which you can use as a base to launch modbus-proxy inside a docker container.
First, build the docker image with:
$ docker build -t modbus-proxy .
Assuming you have prepared a config.yml
in the current directory:
devices:
- modbus:
url: plc1.acme.org:502
listen:
bind: 0:502
The supplied docker image by default runs the command /modbus-proxy-rs -c /etc/modbus-proxy.yml
.
Therefore, running launching a container is as simple as:
docker run --init --rm -p 5020:502 -v $PWD/config.yml:/etc/modbus-proxy.yml modbus-proxy
You can supply a different configuration path (ex: /config.yml
):
docker run --init --rm -p 5020:502 -v $PWD/config.yml:/config.yml modbus-proxy -c /config.yml
Now you should be able to access your modbus device through the modbus-proxy by
connecting your client(s) to <your-hostname/ip>:5020
.
Note that for each modbus device you add in the configuration file you need
to publish the corresponding bind port on the host
(-p <host port>:<container port>
argument).
None yet. Why not be the first?